Electrical Data | SB200 |
Standards | IS/IEC 60898-1 |
Poles | 1P, 2P, 3P, 4P, 1P +N, 3P +N |
Tripping Characteristics | B, C, D |
Rated Current | 0.5A – 63 A |
Rated Voltage |
1P : 230/400/415 V AC
1P + N : 230 V AC 2…4P : 400/415 V AC 3P + N : 400/415 V AC |
Insulation Voltage | 250 V AC (Phase to Ground) 440 V AC (Phase to Phase) |
Max Operating Voltage | 1P: 253 V AC
2…4P : 440 V AC |
Min Operating Voltage | 12 V AC |
Rated Frequency | 50/60 Hz |
Rated Short Circuit Capacity | 10kA |
Energy Limiting Class | 3 |
Over Voltage Category (B,C upto 40A) | III |
Pollution Degree | 2 |
Rated Impulse withstand Voltage | 4kV (Test Voltage 6.2kV at Sea Level, 5kV at 2,000 m) |
Dielectric Test Voltage | 2kV (50/60 Hz, 1 min) |
Accessories mountable | No |